AD-ADAM-6717
8AI/ 5DI/ 4DO Intelligent I/O Gateway
- Linux Open Platform
- 8ch analog input(current or voltage)/5ch digital input/4ch digital output
- Program by linux C API, Node-RED (graphic programming environment)
- Cloud/Database access ,edge data analysis and logic control, data visulization by dashboard
- Interfaces: RS-485x2, Ethernet port x 2 ,1 x USB Type-A 2.0, 1 x USB Micro-B 2.0
Model | ADAM-6717-A |
Analog Input | |
Channels | 8 |
Input Range | ±0.15 V ±0.5 V, ±1 V, ±5 V, ±10 V, ±20 mA, 0~20 mA, 4~20 mA, 0~0.15V, 0~0.5 V, 0~1 V, 0~5 V, 0~10 V |
lnput Type | V, mV, mA |
Resolution(Bits) | 16-bit |
Sampling Rates(S/s) | 100 S/s (sum) |
Environment | |
Isolation Voltage | 2,500 VDC |
Operating Temperature | -40~70 °C (-40~158 °F) |
Ethernet | |
No. of Ports | 2 |
Speed | 10/100 Mbps |
General | |
Connectors | 1 x 9-pin plug-in screw terminal, 2 x 15-pin plug-in screw terminal |
Programming Language | Node-RED, Liunx C |
Hardware | |
I/O | 2 x RS-485, 1 x Micro USB, 1 x USB 2.0 |
OS Support | Linux |
Storage | 1 x micro SD Slot |
Isolated Digital Input | |
Channels | 5 |
Input Voltage | Dry Contact Logic level 1: close to GND Logic level 0: open Wet Contact Logic level 1: 10~30 VDC Logic level 0: 0~3 VDC |
Isolated Digital Output | |
Channels | 4 |
Output Type | Sink |
Output Voltage | 0~30 VDC |
Sink Current | 100 mA max./channel |
Power Requirements | |
Input Voltage | 10~30 VDC |
Application:
Target applications of AD-ADAM-6700 series include factory management, environment monitoring and management, and energy management.
Taking CNC equipment in an electronics factory production line as an example for factory management, AD-ADAM-6700 detects all the operating data of the equipment and improves equipment utilization (OEE), as well as plans predictive maintenance.
In environment monitoring and management, AD-ADAM-6700 can be used to test water quality, read changes in water pressure, and manage wastewater and air pollution.
In energy management applications, AD-ADAM-6700 can be used monitor power consumption of residences, campuses, and factories to manage all power-consumption and distribution, as well as compare results and analyze behaviors.