AD-ADAM-4015

6 RTD Modbus RS-485 Remote I/O Module

Anewtech Systems Advantech Modbus RS-485 Remote I/O Module AD-ADAM-4015
  • 6ch RTD
  • Protocols: Modbus RTU,ASCII
  • Watch dog to recover the system
  • 3000VDC isolation protection
  • Wiring burned-out detection function
Datasheet
Product Specification
Communications
InterfaceRS-485
Environment
Isolation Voltage3,000 VDC
Operating Temperature-10~70 °C (14~158 °F)
General
Connectors2 x 13-pin plug-in screw terminal
ProtocolASCII command, Modbus/RTU
Power Requirements
Input Voltage10~30 VDC
RTD Input
Channels6
Resolution16-bit
Sample Range10 S/s (sum)
Input TypePt 100, Pt 1000, Balco 500, Ni 50, Ni 518, BA1
Hardware
CertificationCE, FCC

A RTD module is popular for temperature measurement. Unlike tranditional designs, AD-ADAM-4015 provides six RTD input channels for different types of RTD signal as an cost-effective solution in industrial & building automation. Occasionally, broken external wiring will lead to inaccurate current value. AD-ADAM-4015 provides a broken wiring detection function so users can easily troubleshoot broken wiring problems.

ADAM-4000/4100 Series Comparison

Series NameADAM-4000 SeriesADAM-4100 Series
Operation Temperature-10 ~ 70°C-40 ~ 85°C
Power Input10 ~ 30VDC10 ~ 48VDC
ESD8KV Air, 4KV contact8KV Air, 6KV contact
EFT2KV4KV
Surge0.5KV4KV
Communication Interface: RS-485YesYes
Communication Interface: USB-Yes
Anewtech-Systems-RS-485-IO-Modules-ADAM-4000-ADAM-4100-Advantech.