AD-ADAM-4021
1AO RS-485 Remote I/O Module. 1ch analog output
- 1ch analog output
- Protocols: ASCII
- Watchdog timer to recover the system
- 3000VDC isolation protection
Model | ADAM-4021-F |
Analog Output | |
Channels | 1 |
Output Ranges | 0~10 V, 0~20 mA, 4~20 mA |
Output Type | V, mA |
Resolution | 12-bit |
Communications | |
Interface | RS-485 |
Environment | |
Isolation Voltage | 3,000 VDC |
Operating Temperature | -10~70 °C (14~158 °F) |
General | |
Connectors | 1 x 10-pin plug-in screw terminal |
Protocol | ASCII command, Modbus/RTU |
Power Requirements | |
Input Voltage | 10~30 VDC |
Hardware | |
Certification | CE, FCC |
Analog output module receives its digital input through an RS-485 interface from the host computer. The format of the data is either engineering units, twos complement hexadecimal format or percentage of full-scale range (FSR), depending on the module ’s configuration. It then uses its microprocessor-controlled D/A converter to convert the digital data into output signals. You get a true readback of the analog output signal from the unit ’s ADC, which independently monitors the output.
You can specify slew rates and start-up currents through the configuration software. The Analog Output Module can supply single-channel analog output in a range of voltages or currents. They protect your equipment from ground loops and power surges by providing opto-isolation of the D/A output. The transformer-based isolation is up to 3000 VDC.
ADAM-4000/4100 Series Comparison
Series Name | ADAM-4000 Series | ADAM-4100 Series |
Operation Temperature | -10 ~ 70°C | -40 ~ 85°C |
Power Input | 10 ~ 30VDC | 10 ~ 48VDC |
ESD | 8KV Air, 4KV contact | 8KV Air, 6KV contact |
EFT | 2KV | 4KV |
Surge | 0.5KV | 4KV |
Communication Interface: RS-485 | Yes | Yes |
Communication Interface: USB | - | Yes |